Dometic marine air conditioner fault codes are three-letter codes on the display: HPF for high pressure, LPF for low pressure, ASF for a failed air sensor, LAC for low AC voltage, PLF for an overheated condenser coil and FIL for a filter due for cleaning. In cooling, Dometic's troubleshooting table traces HPF to seawater flow. The codes below are from Dometic's manual for the MCS6, MCS12 and MCS16 marine climate systems, and the Smart Touch Cabin Control shows the same faults as text.
The fault codes
| Code | Meaning | What Dometic says to check |
|---|---|---|
| HPF | High Freon pressure | Cooling: seawater flow, a plugged strainer or intake, a closed seacock, a kinked hose, the pump and its breaker. Heating: blocked return air, a dirty filter, crushed ducting |
| LPF | Low Freon pressure | Low seawater or return air temperatures, or loss of refrigerant. Check for oil leaks and call a technician |
| ASF | Air sensor fault | The face plate air sensor, the alternate air sensor, the display cable and its sockets |
| LAC | Low AC voltage, if enabled | The supply voltage with a multimeter, and that the voltage setting matches the reading |
| PLF | Condenser coil too hot, if enabled | Water flow to the unit and a fouled condenser, then the water sensor and its socket |
| FIL | Filter needs replacing, if enabled | Replace or clean the filter and reset the filter timer |
HPF isn't shown and doesn't cause a lockout in heat mode. LPF has a 10 minute shutdown delay. On the Smart Touch, the low-pressure fault has a three-minute shutdown delay and the seawater low temperature limit fault shows when the seawater drops below 4 °C (40 °F).
Failsafe levels and lockout
The failsafe level sets which faults are detected and shown, and when the system locks out:
| Level | What happens |
|---|---|
| 0 | Only ASF is detected and shown |
| 1 | All faults detected but not shown. The system stops for 2 minutes or until the fault clears |
| 2 | Faults detected and shown, same 2 minute stop |
| 3 | As level 2, plus a lockout after four consecutive HPF or LPF faults |
To clear a lockout, press the power button once for off and again for on. Dometic recommends the Smart Touch's no-detection level only for initial start-up and troubleshooting, and newer display software returns to full detection after five minutes.
Seawater and the condenser
Dometic's maintenance section asks owners to clean the strainer basket regularly, check the overboard discharge for a steady stream, check the intake scoop and keep hoses free of loops and kinks. Marine growth and scale in the condenser coil block water flow and heat transfer, which leads to HPF and PLF. The manual also asks for the unit to be run in heat for a few seconds once a month to keep the reversing valve free.
For surveyors
Run the air conditioning in cooling at the dock and watch the discharge. A weak stream with HPF on the display is a seawater circuit finding: seacock, strainer, pump or a fouled coil. Look at the seized seacocks and raw water pump leak findings. With Axsail, say "saloon aircon, HPF after 4 minutes in cool, discharge trickling, strainer half full of weed" and it's written up in the systems section.