A Victron VE.Bus error is a numbered fault from a MultiPlus or Quattro inverter charger, shown on a GX device or in the VRM portal. Many of them come from the communication between units, or from wiring on the AC side, and some keep the system off until it's restarted. The meanings below are from Victron's own VE.Bus error code list.
Cable, firmware and system errors
| Code | Meaning | What to check |
|---|---|---|
| Error 1 | Device switched off because another phase switched off | Find the unit that isn't showing error 1. Its LEDs give the real cause, usually low battery, overload or temperature |
| Error 3 | Not all, or more than, the expected devices found | Often follows error 1. Also communication cables, a blown DC fuse on one unit, or two systems joined on one bus |
| Error 4 | No other device found | Seen briefly during a restart. Otherwise the cables |
| Error 6 | Error in an Assistant | Update the firmware and Assistants and reconfigure. Also appears when a VE.Bus BMS is added or removed without changing the Assistant |
| Error 7 | External device connected, Assistant required | A device such as a VE.Bus BMS with no Assistant loaded for it |
| Error 10 | System time synchronisation problem | Usually part of a restart. Also a blown DC fuse on one unit |
| Error 14 | Device cannot transmit data | Most likely a short in the communication cables |
| Error 15 | VE.Bus combination error | Firmware versions that don't match, or BMS commands that clash |
| Error 17 | Phase master missing | Slaves lost the master: network cables and sockets, a blown DC fuse, firmware |
| Error 25 | Incompatible VE.Bus configuration | Units with different firmware, or compatibility IDs that don't match |
| Error 30, Error 31 | Ghost errors | A corrupted message on the bus, usually the RJ45 cables |
AC wiring and relay errors
| Code | Meaning | What to check |
|---|---|---|
| Error 5 | Overvoltage on AC out | AC wiring of a slave unit not connected properly |
| Error 8 | Ground relay test failed | On newer hardware, a unit that keeps showing it has a faulty ground relay. On older units, neutral out tied to ground, a bypassed neutral, or leakage in the loads |
| Error 11 | Relay test fault | Firmware, the input earth, neutral in linked to neutral out, line and neutral swapped on the input |
| Error 18 | AC voltage on the output of a slave that is off | AC wires swapped. There can never be voltage on AC out of a switched-off unit |
| Error 19 | Slave has no AC input | AC input, such as a generator, connected to only one of the synchronised units |
| Error 24 | Switch-over system protection | Too much AC load at switch-over, a slowly sagging generator, a faulty back-feed relay or current sensor |
Errors that keep the system off
Victron's list says most errors restart the system once the cause has gone. Error 16, 18, 19, 20, 22, 24 and 26 keep it off until it's restarted, and error 25 until it's configured correctly. To restart, switch every unit off one at a time with the switch on its front, then switch them all on. For error 24 on a system of several units, Victron's advice is to record the LEDs on video before resetting, then measure across each unit's AC terminals with the wiring removed: a faulty unit shows close to zero ohms between line in and line out.
For surveyors
On a boat, error 11 and error 18 point to the shore power and generator wiring as much as to the inverter, so check them with the reverse polarity and galvanic isolator findings. Hand-crimped network leads between parallel units are worth a photograph on their own. With Axsail, say "MultiPlus, VE.Bus error 11 logged at switch-over to shore power" and it's written into the electrical section with the right recommendation.