Victron VE.Bus error codes: what error 1, 3, 8, 11, 17 and 24 mean on a MultiPlus or Quattro

UPDATED 16 NOVEMBER 2026 · 2 FINDINGS · 2 SOURCES

Victron VE.Bus error codes for MultiPlus and Quattro inverter chargers: error 11 relay test, error 24 switch-over protection, and which codes keep the system off.

AT A GLANCE
Victron MultiPlus and Quattro (VE.Bus)
MAKER
Victron Energy
COVERS
VE.Bus inverter chargers, such as the MultiPlus, MultiPlus-II, Quattro and EasySolar-II, single or in parallel, split and three-phase systems
WHERE THE CODE SHOWS
On a GX device and the VRM portal as "VE.Bus Error" with a number. The unit's own LEDs show it too; Victron recommends its Toolkit app to decode the LED codes
CHECK FIRST
The communication cables, any blown DC fuse on one unit, and that every unit runs the same firmware

A Victron VE.Bus error is a numbered fault from a MultiPlus or Quattro inverter charger, shown on a GX device or in the VRM portal. Many of them come from the communication between units, or from wiring on the AC side, and some keep the system off until it's restarted. The meanings below are from Victron's own VE.Bus error code list.

Cable, firmware and system errors

Code Meaning What to check
Error 1 Device switched off because another phase switched off Find the unit that isn't showing error 1. Its LEDs give the real cause, usually low battery, overload or temperature
Error 3 Not all, or more than, the expected devices found Often follows error 1. Also communication cables, a blown DC fuse on one unit, or two systems joined on one bus
Error 4 No other device found Seen briefly during a restart. Otherwise the cables
Error 6 Error in an Assistant Update the firmware and Assistants and reconfigure. Also appears when a VE.Bus BMS is added or removed without changing the Assistant
Error 7 External device connected, Assistant required A device such as a VE.Bus BMS with no Assistant loaded for it
Error 10 System time synchronisation problem Usually part of a restart. Also a blown DC fuse on one unit
Error 14 Device cannot transmit data Most likely a short in the communication cables
Error 15 VE.Bus combination error Firmware versions that don't match, or BMS commands that clash
Error 17 Phase master missing Slaves lost the master: network cables and sockets, a blown DC fuse, firmware
Error 25 Incompatible VE.Bus configuration Units with different firmware, or compatibility IDs that don't match
Error 30, Error 31 Ghost errors A corrupted message on the bus, usually the RJ45 cables

AC wiring and relay errors

Code Meaning What to check
Error 5 Overvoltage on AC out AC wiring of a slave unit not connected properly
Error 8 Ground relay test failed On newer hardware, a unit that keeps showing it has a faulty ground relay. On older units, neutral out tied to ground, a bypassed neutral, or leakage in the loads
Error 11 Relay test fault Firmware, the input earth, neutral in linked to neutral out, line and neutral swapped on the input
Error 18 AC voltage on the output of a slave that is off AC wires swapped. There can never be voltage on AC out of a switched-off unit
Error 19 Slave has no AC input AC input, such as a generator, connected to only one of the synchronised units
Error 24 Switch-over system protection Too much AC load at switch-over, a slowly sagging generator, a faulty back-feed relay or current sensor

Errors that keep the system off

Victron's list says most errors restart the system once the cause has gone. Error 16, 18, 19, 20, 22, 24 and 26 keep it off until it's restarted, and error 25 until it's configured correctly. To restart, switch every unit off one at a time with the switch on its front, then switch them all on. For error 24 on a system of several units, Victron's advice is to record the LEDs on video before resetting, then measure across each unit's AC terminals with the wiring removed: a faulty unit shows close to zero ohms between line in and line out.

For surveyors

On a boat, error 11 and error 18 point to the shore power and generator wiring as much as to the inverter, so check them with the reverse polarity and galvanic isolator findings. Hand-crimped network leads between parallel units are worth a photograph on their own. With Axsail, say "MultiPlus, VE.Bus error 11 logged at switch-over to shore power" and it's written into the electrical section with the right recommendation.

Findings to look for on Victron MultiPlus and Quattro (VE.Bus)

Each page shows how the defect is found, what decides the grade and example findings written up at A, B and C.

ELECTRICAL

Shore power reverse polarity

What reverse polarity on a boat's shore power means, why breakers stop protecting you, the ABYC reverse polarity indicator, how a surveyor tests it and three example findings graded A, B and C.

How to find and write it up
ELECTRICAL

No galvanic isolator

How the shore power earth links your boat's underwater metals to every boat on the dock, what a galvanic isolator does, what ABYC A-28 asks for, what one costs and three example findings graded A, B and C.

How to find and write it up

Frequently asked

What is VE.Bus error 24 on a Victron MultiPlus?

Switch-over system protection. Victron says a unit has measured current through its back-feed relay while the relay should be open. The likely causes are too much AC load when the relay has to open, an AC input that sags slowly before it's rejected, often from a generator, or a faulty relay or current sensor. The system stays off until restarted.

What is VE.Bus error 11?

A failed self-test of the relays in a MultiPlus-II or EasySolar-II. Victron says it's often an installation or wiring issue: update the firmware first, then check the earth on the AC input, any external link between neutral in and neutral out, and whether line and neutral are swapped on the input.

How do I clear a Victron VE.Bus error?

Many VE.Bus errors restart the system once the cause is gone. Others, such as error 16, 18, 19, 22, 24 and 26, keep it off until it's restarted. Victron's restart is to switch every unit off one by one with its front switch, then switch them all on again.

Why do VE.Bus errors keep appearing on a parallel or three-phase system?

Victron names the network cables first: self-crimped RJ45 leads are a known cause of several VE.Bus errors, so use factory-made cables. A blown DC fuse on one unit is the other common cause, because that unit drops off the network as soon as shore power or the generator stops.

Your full survey report, minutes after the walk-round

Dictate as you inspect. Axsail builds the findings and the report for your signature

Start free

More fault codes

All fault codes
CHARGERS, INVERTERS AND BATTERIES

Victron MPPT solar chargers

Victron MPPT error codes from Victron's own list: battery and PV errors, Err 67 BMS connection lost, Err 116, and which codes reset by themselves.

Look up a code
CHARGERS, INVERTERS AND BATTERIES

Victron BatteryProtect

Victron BatteryProtect and Smart BatteryProtect error codes: E1 to E4 on every model, E0 and E5 to E8 on the Smart versions, and the P2 and P3 warnings.

Look up a code
CHARGERS, INVERTERS AND BATTERIES

Victron Lynx Smart BMS

Victron Lynx Smart BMS error codes from Victron's manual: what 1 to 14 red LED flashes mean, the W-B warnings, A-B alarms, E-B errors and blown fuse alarms.

Look up a code
CHARGERS, INVERTERS AND BATTERIES

Victron Phoenix Inverter Smart

Victron Phoenix inverter error codes from Victron's manual: each LED pattern for overload, battery voltage, temperature and DC ripple, and the restarts.

Look up a code
CHARGERS, INVERTERS AND BATTERIES

Victron Orion XS DC-DC charger

Victron Orion XS error codes from Victron's manual: battery temperature, terminal overheated, BMS connection lost (error 67) and the 150 to 161 warnings.

Look up a code
CHARGERS, INVERTERS AND BATTERIES

Victron Cerbo GX and GX devices

Victron Cerbo GX error codes from Victron's manual: #42 storage corrupt, #46 data partition full, #48 DVCC firmware, #51 MK3 update and #60 MFD connection.

Look up a code

Standards to check against

ABYC E-11

AC and DC Electrical Systems on Boats

What ABYC E-11 covers on a boat's AC and DC systems, the rules surveyors check most often, from the 7 inch battery fuse rule to the reverse polarity indicator, and how to cite E-11 in a finding.

What surveyors check