Victron Lynx Smart BMS error codes come in two forms: red flashes of the Status LED, from 1 to 14 every 4 seconds, and coded messages in the VictronConnect app. The app codes start W for a warning, A for an alarm that has shut the system down and E for an error, followed by B for the BMS, D for a Lynx Distributor or F for a fuse. The meanings below are from Victron's Lynx Smart BMS manual.
Red LED flashes
| Red flashes every 4 seconds | Meaning | What to check |
|---|---|---|
| 1 | Warning | Open VictronConnect for the warning code |
| 2 | Battery communication error | The battery BMS cables |
| 3 | High or low cell voltage, or high or low temperature | Cell voltages and battery temperature in VictronConnect |
| 4 | High BMS temperature | Ambient temperature and the BMS fans |
| 5 | Pre-charge time out | Too much DC load capacitance on the output |
| 6 | Pre-charge high current | A load drawing current during pre-charge |
| 7 | Probably wrong system voltage | The battery voltage settings |
| 8 | Contactor current too high | The load and charge currents against the rating |
| 9 | Initialisation error | Battery connections |
| 10 | Safety contactor failure | Contact a Victron dealer |
| 12 | Internal supply error | Contact a Victron dealer |
| 14 | Battery voltage not allowed | The battery voltage, outside every system range |
Green and red alternating means the unit is in bootloader mode for a firmware update. Orange blinking is a delayed shutdown while the pre-charge circuit cools.
Warnings, alarms and errors in VictronConnect
| Code | Message | Victron's instruction |
|---|---|---|
| W-B01 | Low cell voltage | Charge the battery or reduce the load before the system shuts down |
| W-B02 | High current | Reduce the load or turn loads off |
| W-B03 | High BMS temperature | Check the ambient temperature and that the fans run |
| W-B06 | Load will disconnect | Loads go off in 30 seconds unless the cause is fixed |
| W-B07 | Low SoC | Charge the battery or reduce the load |
| W-D01 to W-D08 | Communication with distributor A to H lost | The cable between BMS and distributor |
| A-B01 | Low cell voltage | Charge the battery. Loads come back on once it's charged |
| A-B02 | High current | Reduce charge current or loads. Retries after 5 minutes |
| A-B06 | Load disconnected | Charge the battery. If unresolved, the contactor opens |
| A-F01 to A-F32 | Fuse blown in a Lynx Distributor | Check the circuit and replace the fuse |
| E-B02 | No battery found | Check the BMS cable loop is closed |
| E-B09 | Battery voltage not allowed | Outside every system range, below 9 V or above 60 V |
| E-B25 | Pre-charge error | Load resistance too low. Disconnect or reduce DC loads |
| E-B32 | BMS cable error | The battery M8 cabling |
| E-B34 | Wrong system voltage | The battery voltage settings in VictronConnect |
| E-B36 | ATC/ATD failure | Every load and charger must be controlled by ATC or ATD |
| E-B119 | Settings data lost | Reset the settings to defaults |
E-B11 hardware error, E-B26 contactor error and E-B116 calibration data lost all need a Victron dealer, according to the manual.
How the BMS switches the boat off
The Lynx Smart BMS uses its ATD output to turn loads off and ATC to stop chargers. W-B06 gives 30 seconds' notice before the loads go. If the battery keeps falling after that, the contactor opens and the whole DC system is disconnected. E-B36 says a charger or load isn't on the ATC or ATD control, so the BMS can't protect the battery from it.
For surveyors
On a lithium installation, the alarm history in VictronConnect shows how the bank has been used: repeated A-B01 entries mean it's been run down to cell cut-off. Check every charging source is on ATC and every load on ATD, as E-B36 requires, and compare the installation with the lithium batteries without a BMS finding. With Axsail, say "Lynx Smart BMS, 3 red flashes, cell 4 low in VictronConnect" as you photograph the screen.