Victron Lynx Smart BMS error codes from Victron's manual: what 1 to 14 red LED flashes mean, the W-B warnings, A-B alarms, E-B errors and blown fuse alarms.

AT A GLANCE
Victron Lynx Smart BMS
MAKER
Victron Energy
COVERS
The Lynx Smart BMS with Victron Smart Lithium batteries, and the Lynx Distributors connected to it
WHERE THE CODE SHOWS
As red flashes of the Status LED, repeated every 4 seconds, and as a coded message in the VictronConnect app, on a GX device and in VRM
CHECK FIRST
The battery M8 BMS cables and the cell voltages in VictronConnect, then the ATC and ATD wiring to chargers and loads

Victron Lynx Smart BMS error codes come in two forms: red flashes of the Status LED, from 1 to 14 every 4 seconds, and coded messages in the VictronConnect app. The app codes start W for a warning, A for an alarm that has shut the system down and E for an error, followed by B for the BMS, D for a Lynx Distributor or F for a fuse. The meanings below are from Victron's Lynx Smart BMS manual.

Red LED flashes

Red flashes every 4 seconds Meaning What to check
1 Warning Open VictronConnect for the warning code
2 Battery communication error The battery BMS cables
3 High or low cell voltage, or high or low temperature Cell voltages and battery temperature in VictronConnect
4 High BMS temperature Ambient temperature and the BMS fans
5 Pre-charge time out Too much DC load capacitance on the output
6 Pre-charge high current A load drawing current during pre-charge
7 Probably wrong system voltage The battery voltage settings
8 Contactor current too high The load and charge currents against the rating
9 Initialisation error Battery connections
10 Safety contactor failure Contact a Victron dealer
12 Internal supply error Contact a Victron dealer
14 Battery voltage not allowed The battery voltage, outside every system range

Green and red alternating means the unit is in bootloader mode for a firmware update. Orange blinking is a delayed shutdown while the pre-charge circuit cools.

Warnings, alarms and errors in VictronConnect

Code Message Victron's instruction
W-B01 Low cell voltage Charge the battery or reduce the load before the system shuts down
W-B02 High current Reduce the load or turn loads off
W-B03 High BMS temperature Check the ambient temperature and that the fans run
W-B06 Load will disconnect Loads go off in 30 seconds unless the cause is fixed
W-B07 Low SoC Charge the battery or reduce the load
W-D01 to W-D08 Communication with distributor A to H lost The cable between BMS and distributor
A-B01 Low cell voltage Charge the battery. Loads come back on once it's charged
A-B02 High current Reduce charge current or loads. Retries after 5 minutes
A-B06 Load disconnected Charge the battery. If unresolved, the contactor opens
A-F01 to A-F32 Fuse blown in a Lynx Distributor Check the circuit and replace the fuse
E-B02 No battery found Check the BMS cable loop is closed
E-B09 Battery voltage not allowed Outside every system range, below 9 V or above 60 V
E-B25 Pre-charge error Load resistance too low. Disconnect or reduce DC loads
E-B32 BMS cable error The battery M8 cabling
E-B34 Wrong system voltage The battery voltage settings in VictronConnect
E-B36 ATC/ATD failure Every load and charger must be controlled by ATC or ATD
E-B119 Settings data lost Reset the settings to defaults

E-B11 hardware error, E-B26 contactor error and E-B116 calibration data lost all need a Victron dealer, according to the manual.

How the BMS switches the boat off

The Lynx Smart BMS uses its ATD output to turn loads off and ATC to stop chargers. W-B06 gives 30 seconds' notice before the loads go. If the battery keeps falling after that, the contactor opens and the whole DC system is disconnected. E-B36 says a charger or load isn't on the ATC or ATD control, so the BMS can't protect the battery from it.

For surveyors

On a lithium installation, the alarm history in VictronConnect shows how the bank has been used: repeated A-B01 entries mean it's been run down to cell cut-off. Check every charging source is on ATC and every load on ATD, as E-B36 requires, and compare the installation with the lithium batteries without a BMS finding. With Axsail, say "Lynx Smart BMS, 3 red flashes, cell 4 low in VictronConnect" as you photograph the screen.

Findings to look for on Victron Lynx Smart BMS

Each page shows how the defect is found, what decides the grade and example findings written up at A, B and C.

ELECTRICAL

Lithium batteries without a BMS

What ABYC E-13 asks of lithium battery systems on boats, why a battery management system is required, what a surveyor checks on a lithium install and three example findings graded A, B and C.

How to find and write it up
ELECTRICAL

Missing overcurrent protection

Why an unfused battery cable is a fire risk, the ABYC E-11 rule surveyors check against, which fuse types suit which battery banks, what the fix costs and three example findings graded A, B and C.

How to find and write it up

Frequently asked

What does the red LED flashing 3 times mean on a Lynx Smart BMS?

Victron's manual says 3 red flashes every 4 seconds means a high or low cell voltage or a high or low temperature has been detected in the batteries. Open VictronConnect to see which, then charge the battery or reduce the load.

What is the difference between a warning and an alarm on a Lynx Smart BMS?

Victron says a warning (W-) is a problem that will shut the system down if it isn't corrected, while an alarm (A-) gives the reason the system has already shut down. Errors (E-) are faults in the installation or the unit itself.

What is error E-B25 on a Lynx Smart BMS?

Pre-charge error: the load resistance is too low for the BMS to pre-charge the loads before the contactor closes. Victron's advice is to disconnect or reduce some DC loads. E-B35, pre-charge timeout, is the same problem with too much load capacitance.

What does A-F01 mean on a Victron Lynx?

A blown fuse in a Lynx Distributor connected to the Lynx Smart BMS. The number is the fuse position, from A-F01 to A-F32 across up to 8 distributors. Check the circuit, then replace the fuse.

Your full survey report, minutes after the walk-round

Dictate as you inspect. Axsail builds the findings and the report for your signature

Start free

More fault codes

All fault codes
CHARGERS, INVERTERS AND BATTERIES

Victron BatteryProtect

Victron BatteryProtect and Smart BatteryProtect error codes: E1 to E4 on every model, E0 and E5 to E8 on the Smart versions, and the P2 and P3 warnings.

Look up a code
CHARGERS, INVERTERS AND BATTERIES

Victron MultiPlus and Quattro (VE.Bus)

Victron VE.Bus error codes for MultiPlus and Quattro inverter chargers: error 11 relay test, error 24 switch-over protection, and which codes keep the system off.

Look up a code
CHARGERS, INVERTERS AND BATTERIES

Victron MPPT solar chargers

Victron MPPT error codes from Victron's own list: battery and PV errors, Err 67 BMS connection lost, Err 116, and which codes reset by themselves.

Look up a code
CHARGERS, INVERTERS AND BATTERIES

Victron Phoenix Inverter Smart

Victron Phoenix inverter error codes from Victron's manual: each LED pattern for overload, battery voltage, temperature and DC ripple, and the restarts.

Look up a code
CHARGERS, INVERTERS AND BATTERIES

Victron Orion XS DC-DC charger

Victron Orion XS error codes from Victron's manual: battery temperature, terminal overheated, BMS connection lost (error 67) and the 150 to 161 warnings.

Look up a code
CHARGERS, INVERTERS AND BATTERIES

Victron Cerbo GX and GX devices

Victron Cerbo GX error codes from Victron's manual: #42 storage corrupt, #46 data partition full, #48 DVCC firmware, #51 MK3 update and #60 MFD connection.

Look up a code

Standards to check against

ABYC E-11

AC and DC Electrical Systems on Boats

What ABYC E-11 covers on a boat's AC and DC systems, the rules surveyors check most often, from the 7 inch battery fuse rule to the reverse polarity indicator, and how to cite E-11 in a finding.

What surveyors check