A Victron MPPT error code is a number the solar charger reports when it stops or limits charging to protect itself or the battery. You read it in the VictronConnect app or on a GX device. Some errors clear on their own once the cause has gone, others need a restart or point to a faulty unit. The meanings below are from Victron's own error code list, which also covers Skylla chargers, the Inverter RS and Multi RS, and the Orion Smart DC-DC charger.
Battery side errors
| Code | Meaning | What to check |
|---|---|---|
| Err 1 | Battery temperature too high | Clears once the battery cools. The reading comes from an external sensor, such as a Smart Battery Sense or BMV, or from the charger itself |
| Err 2 | Battery voltage too high | Another charger on the same battery, a fault in the controller, or a battery voltage setting lower than the battery fitted |
| Err 3, Err 4 | Remote temperature sensor failure | The T-sense connector, most likely wired to BAT+ or BAT- by mistake |
| Err 5 | Remote temperature sensor connection lost | The T-sense connection. Doesn't clear by itself |
| Err 6, Err 7 | Remote battery voltage sense failure | The V-sense connector, most likely wired in reverse polarity |
| Err 8 | Remote voltage sense connection lost | The V-sense connection to the battery terminals |
| Err 14 | Battery low temperature | Charging stopped so a LiFePO4 battery isn't charged in the cold, which damages the cells |
| Err 29 | Over-charge protection | Too many panels in series, absorption and float settings that don't match the battery, or another charger pushing the voltage up |
| Err 67 | BMS connection lost | The charger is set for BMS control but gets no messages: check the BMS link. The setting survives a power cycle |
Charger and PV side errors
| Code | Meaning | What to check |
|---|---|---|
| Err 17 | Controller overheated despite reduced current | Ambient temperature and anything blocking the heatsink |
| Err 18 | Controller over-current | A large load switched on the battery side, or an overloaded inverter. Restart after 3 minutes if it doesn't clear |
| Err 21 | Current sensor issue | Reconnect all wires. Victron says the controller is probably faulty if it stays |
| Err 26 | Terminal overheated | The power terminals: cable type, strands and tight bolts |
| Err 27 | Charger short circuit | Over-current on the battery side, for example a battery switched in through a contactor |
| Err 28 | Power stage issue | Reconnect all wires. If it stays, Victron says the unit needs replacing |
| Err 33 | PV over-voltage | The array's open-circuit voltage is too close to the charger's limit: rearrange the panels |
| Err 34 | PV over-current | Restart after 3 minutes. If it stays, the controller is probably faulty |
| Err 38, Err 39, Err 80 to 87 | PV input shutdown | The PV input is shorted to protect the battery. Usually a wrong battery voltage setting, or another charger set higher |
| Err 40 | PV input failed to shut down | The charger disconnects its own output and becomes faulty |
| Err 114 | CPU temperature too high | Ventilation around the cabinet |
| Err 116 | Calibration data lost | Serious only if active and the unit won't work |
| Err 117 | Incompatible firmware | A firmware update didn't finish: run it again |
| Err 119 | Settings data lost | Reset to factory defaults, power off for 3 minutes, reconfigure |
The Inverter RS and Multi RS have their own codes in the same list: Err 50 and 52 for overload, Err 51 for inverter temperature, Err 53 and 54 for low output voltage, and Err 69 to 77 for networked units that don't match.
Errors that clear by themselves
Victron's list marks some errors as auto-reset: battery temperature (Err 1), battery voltage (Err 2), terminal overheating (Err 26) and PV over-voltage (Err 33) among them. Others stay until someone acts: Err 5, Err 21, Err 28 and Err 119 never clear on their own. For a solar charger, Err 67 appears only when there's sun, so a lasting BMS problem shows each morning and disappears at night.
For surveyors
An error in the charger's history isn't the same as a fault today, so note whether it's active. A charger showing Err 2 or Err 29 next to a second charger, or Err 67 on a lithium bank, says more about the system than the charger. Check it against the lithium batteries without a BMS finding and the ABYC E-11 rules for overcurrent protection. With Axsail, say "solar charger, Err 67 active, BMS cable unplugged at the GX" as you photograph the screen and it goes into the electrical section.