Victron Phoenix inverter error codes on the Phoenix Inverter Smart are shown by two LEDs: the red Alarm LED says which protection it is, and the green Inverter LED says whether it's still a warning or the inverter has shut down. Green steady means a warning. Green blinking with a fast double pulse means the inverter has switched off on that alarm. The patterns below are from Victron's Phoenix Inverter Smart manual.
LED patterns
| Red Alarm LED | Green LED steady: warning | Green LED fast double pulse: alarm, inverter off |
|---|---|---|
| On | Overload warning: AC load above the rating | Overload alarm: shut down, no automatic restart |
| Slow blinking | Low battery voltage warning | Low battery voltage alarm |
| Fast blinking | High battery voltage warning | High battery voltage alarm |
| Double pulse | High temperature warning | High temperature alarm |
| Fast single pulse | High DC ripple warning | DC ripple alarm |
Other states from the same table: all LEDs off means the inverter is switched off, has its remote on/off loop open or has no DC supply. Green blinking with the yellow ECO LED on is ECO mode searching for a load. Green and red both blinking means a firmware update is running or has failed.
What to check for each alarm
| Alarm | Victron's checks |
|---|---|
| Overload | Reduce the AC load. Motors and pumps with a high start-up current can trip it |
| Low battery voltage | Charge the battery, turn AC loads off, check the cable connections are tight and the cables thick enough |
| High battery voltage | The battery bank wiring, and chargers, alternators or solar chargers with a faulty regulator |
| High temperature | Reduce the AC load or move the inverter somewhere better ventilated |
| DC ripple | Loose DC connections or cables that are too thin, and that the fuses and battery isolators work |
Restarts and lock-outs
Most alarms clear themselves. After a low battery, high temperature or high battery shutdown, the inverter waits at least 30 seconds and restarts when the condition has gone. Overload and DC ripple are different: after 3 restarts and a fourth trip within 30 seconds, the inverter stays off until someone switches it off and on again. Victron adds that continuous high DC ripple shortens the inverter's life.
For surveyors
A DC ripple or low battery alarm on an inverter that's otherwise healthy usually points to the cables and the battery, so look at cable size against the inverter's rating, the fuse close to the battery and the terminal lugs. Note the alarm history in VictronConnect if the owner can connect. With Axsail, say "Phoenix inverter, red alarm LED fast single pulse, DC ripple, 25 mm² cables on a 3000 VA unit" and it goes into the electrical section.