A Victron BatteryProtect error code is a letter and number on the unit's display, E for an error that has switched the load off and P for a warning that it's about to. E1 to E4 appear on every model. The Smart BatteryProtect adds E0 and E5 to E8, plus the P2 and P3 warnings, and shows them in the VictronConnect app as well. The meanings below are from Victron's manuals for each model.
Error and warning codes
| Code | Meaning | What to check |
|---|---|---|
| E0 | Calibration failure | Internal fault. Victron says the unit can't be repaired by the user and needs replacing |
| E1 | Short circuit | A short, an overload or the inrush of an inverter powered directly. Check the load against the rating, then the cables |
| E2 | Over temperature | Load current, loose or high resistance connections, and a hot or radiant location |
| P2 | Over temperature warning | Internal temperature close to the limit: act before the load is cut |
| E3 | Under voltage | Input below the set limit for 90 seconds. Recharge the battery and check the charging system |
| P3 | Under voltage warning | Under voltage disconnection in 90 seconds unless something changes |
| E4 | Over voltage | Input above 16 V on a 12 V system, 32 V on 24 V or 64 V on the 48 V model. Check the chargers' voltage settings |
| E5 | Configuration failure | Reset to factory defaults, disconnect all power for 3 minutes, reconfigure |
| E6 | Reference voltage failure | Internal fault, unit needs replacing |
| E7 | BMS lockout | The BMS switched it off and on 3 times in a row. Check the BMS log and the Remote terminal wire |
| E8 | Reverse current | Unit fitted the wrong way round, or a charging source on the OUT side |
The older BatteryProtect 12/24V lists only E1 to E4. The Smart BatteryProtect 48V manual counts 9 error modes and 2 warnings.
Inverters and inrush current
E1 on a BatteryProtect wired straight to an inverter is a common pairing in the manual's own wording: the inverter's inrush trips the short circuit protection. Victron's advice is to leave the inverter on its own fused supply and use the BatteryProtect to drive the inverter's remote on/off terminal.
For surveyors
A BatteryProtect on a lithium bank is often the load disconnect the BMS relies on, so E7 or repeated E3 entries say the bank is being run flat. Check the installation against the lithium batteries without a BMS finding, and look for a fuse ahead of the unit as ABYC E-11 requires. With Axsail, say "BatteryProtect on the house loads showing E1, inverter wired through it directly" as you photograph the display.