Victron BatteryProtect error codes: E1 short circuit, E2 over temperature, E3 under voltage, E7 BMS lockout and the rest

UPDATED 16 NOVEMBER 2026 · 2 FINDINGS · 3 SOURCES

Victron BatteryProtect and Smart BatteryProtect error codes: E1 to E4 on every model, E0 and E5 to E8 on the Smart versions, and the P2 and P3 warnings.

AT A GLANCE
Victron BatteryProtect
MAKER
Victron Energy
COVERS
BatteryProtect 12/24V and 48V, Smart BatteryProtect 12/24V and Smart BatteryProtect 48V
WHERE THE CODE SHOWS
On the unit's 7-segment display, and in the VictronConnect app on the Smart models. The display stops showing an error after 5 minutes to save power
CHECK FIRST
The load current against the unit's rating, loose or undersized cables, and which way round the unit is fitted

A Victron BatteryProtect error code is a letter and number on the unit's display, E for an error that has switched the load off and P for a warning that it's about to. E1 to E4 appear on every model. The Smart BatteryProtect adds E0 and E5 to E8, plus the P2 and P3 warnings, and shows them in the VictronConnect app as well. The meanings below are from Victron's manuals for each model.

Error and warning codes

Code Meaning What to check
E0 Calibration failure Internal fault. Victron says the unit can't be repaired by the user and needs replacing
E1 Short circuit A short, an overload or the inrush of an inverter powered directly. Check the load against the rating, then the cables
E2 Over temperature Load current, loose or high resistance connections, and a hot or radiant location
P2 Over temperature warning Internal temperature close to the limit: act before the load is cut
E3 Under voltage Input below the set limit for 90 seconds. Recharge the battery and check the charging system
P3 Under voltage warning Under voltage disconnection in 90 seconds unless something changes
E4 Over voltage Input above 16 V on a 12 V system, 32 V on 24 V or 64 V on the 48 V model. Check the chargers' voltage settings
E5 Configuration failure Reset to factory defaults, disconnect all power for 3 minutes, reconfigure
E6 Reference voltage failure Internal fault, unit needs replacing
E7 BMS lockout The BMS switched it off and on 3 times in a row. Check the BMS log and the Remote terminal wire
E8 Reverse current Unit fitted the wrong way round, or a charging source on the OUT side

The older BatteryProtect 12/24V lists only E1 to E4. The Smart BatteryProtect 48V manual counts 9 error modes and 2 warnings.

Inverters and inrush current

E1 on a BatteryProtect wired straight to an inverter is a common pairing in the manual's own wording: the inverter's inrush trips the short circuit protection. Victron's advice is to leave the inverter on its own fused supply and use the BatteryProtect to drive the inverter's remote on/off terminal.

For surveyors

A BatteryProtect on a lithium bank is often the load disconnect the BMS relies on, so E7 or repeated E3 entries say the bank is being run flat. Check the installation against the lithium batteries without a BMS finding, and look for a fuse ahead of the unit as ABYC E-11 requires. With Axsail, say "BatteryProtect on the house loads showing E1, inverter wired through it directly" as you photograph the display.

Findings to look for on Victron BatteryProtect

Each page shows how the defect is found, what decides the grade and example findings written up at A, B and C.

ELECTRICAL

Lithium batteries without a BMS

What ABYC E-13 asks of lithium battery systems on boats, why a battery management system is required, what a surveyor checks on a lithium install and three example findings graded A, B and C.

How to find and write it up
ELECTRICAL

Missing overcurrent protection

Why an unfused battery cable is a fire risk, the ABYC E-11 rule surveyors check against, which fuse types suit which battery banks, what the fix costs and three example findings graded A, B and C.

How to find and write it up

Frequently asked

What does E1 mean on a Victron BatteryProtect?

Short circuit protection: a short, an overload or a high inrush current, such as when the BatteryProtect powers an inverter directly. Victron's manual says to check the load against the unit's rating, use the BatteryProtect to switch the inverter's remote on/off input instead, and check for loose or undersized cables.

What is E3 on a Victron BatteryProtect?

Under voltage: the input voltage stayed below the selected limit for 90 seconds, so the load was disconnected. Switch off the loads and recharge the battery, then check the charging system. On the Smart models, warning P3 comes first, 90 seconds before the disconnection.

What is E7 BMS lockout on a Smart BatteryProtect?

The battery's BMS asked the Smart BatteryProtect to disconnect and reconnect 3 times in a row, typically during a low cell voltage shutdown. It then stays off until the input is above 13 V on a 12 V system or 26 V on a 24 V system. Check the BMS log and the wire to the Remote terminal.

Can a Victron BatteryProtect be used between two batteries?

No. Victron's Smart BatteryProtect manual says current must only flow from IN to OUT, and reverse current, which flows whenever the output voltage is higher than the input, can damage it permanently. Error E8 shows when reverse current is detected.

Your full survey report, minutes after the walk-round

Dictate as you inspect. Axsail builds the findings and the report for your signature

Start free

More fault codes

All fault codes
CHARGERS, INVERTERS AND BATTERIES

Victron MPPT solar chargers

Victron MPPT error codes from Victron's own list: battery and PV errors, Err 67 BMS connection lost, Err 116, and which codes reset by themselves.

Look up a code
CHARGERS, INVERTERS AND BATTERIES

Victron MultiPlus and Quattro (VE.Bus)

Victron VE.Bus error codes for MultiPlus and Quattro inverter chargers: error 11 relay test, error 24 switch-over protection, and which codes keep the system off.

Look up a code
CHARGERS, INVERTERS AND BATTERIES

Victron Lynx Smart BMS

Victron Lynx Smart BMS error codes from Victron's manual: what 1 to 14 red LED flashes mean, the W-B warnings, A-B alarms, E-B errors and blown fuse alarms.

Look up a code
CHARGERS, INVERTERS AND BATTERIES

Victron Phoenix Inverter Smart

Victron Phoenix inverter error codes from Victron's manual: each LED pattern for overload, battery voltage, temperature and DC ripple, and the restarts.

Look up a code
CHARGERS, INVERTERS AND BATTERIES

Victron Orion XS DC-DC charger

Victron Orion XS error codes from Victron's manual: battery temperature, terminal overheated, BMS connection lost (error 67) and the 150 to 161 warnings.

Look up a code
CHARGERS, INVERTERS AND BATTERIES

Victron Cerbo GX and GX devices

Victron Cerbo GX error codes from Victron's manual: #42 storage corrupt, #46 data partition full, #48 DVCC firmware, #51 MK3 update and #60 MFD connection.

Look up a code

Standards to check against

ABYC E-11

AC and DC Electrical Systems on Boats

What ABYC E-11 covers on a boat's AC and DC systems, the rules surveyors check most often, from the 7 inch battery fuse rule to the reverse polarity indicator, and how to cite E-11 in a finding.

What surveyors check